System Cable Tube
The System Cable Tube is a particularly easy-to-install cable box made of two pipe half-shells with a click lock and an inner fire protection fabric. Suitable as a fireproof penetration sealing system for electrical cables and lines of all types, electrical installation conduits, and HVAC split lines. Fire-resistant up to max. 120 minutes.
Areas of application
Cable box for the fire sealing of cables and electrical lines in:
- Plasterboard walls
- Solid walls
- Solid floors
- Timber construction (CLT walls and floors)
Highlights
- The entire cross-section of the cable tubes can be used
- Easy retrofitting possible
- Easy installation, as no additional measures for the aperture edge required
- Installation around existing lines also possible
- Also suitable for cable penetration seals in timber construction
Fire resistance class
Max. EI 120 acc. to EN 13501-2
Certificate
ETA-22/0053: 7/10/24
Features
- Single or group arrangement for sealing existing lines or as a reserve penetration seal for future installations
- Various diameters and lengths available
- Suitable for 68 mm socket holes or 100 mm core drill holes
- Easy to reuse without special tools
- The plastic half-shells are connected to each other using a click lock
Downloads
Application data sheets / Installation manuals / Certificates
Installation video: System Cable Tube
The system Cable Tube serves to seal penetrations of cables of any type as well as lines of split-line air conditioning systems. Once the Cable Tube is installed in place, it is sealed with the dedicated sealing plug and with fire protection filler FLAMMOTECT-A. System Cable Tube meets the fire resistance requirements of up to class EI 120 as defined in standard EN 13501-2.
System information
Technical data
General
Brand name
FLAMRO Brandschutz Vertriebs GmbH
Thickness of building element
Building element
Plasterboard wall, solid wall
Thickness of building element
≥ 100 mm
Building element
Timber wall
Thickness of building element
≥ 100 mm
Building element
Solid floor
Thickness of building element
≥ 125 mm
Building element
Timber floor
Thickness of building element
≥ 140 mm
Penetration seal thickness
Building element
Plasterboard wall, solid wall, solid floor, timber wall, timber floor
Strength
≥ 150 mm
Data line
Combustible pipe Ø
Diameter Ø
≤ 32 mm
Electrical installation conduits, single Ø
Single Ø
≤ 63 mm
Cable Ø
≤ 21 mm
Coaxial cables / wave guides Ø
Diameter Ø
≤ 28.5 mm
Cable Ø
Diameter Ø
≤ 80 mm
General
HVAC split line combinations
yes
speedpipes
Diameter Ø
≤ 7 mm
Number
≤ 24
Diameter Ø
≤ 10 mm
Number
≤ 7
Diameter Ø
≤ 12 mm
Number
≤ 5
Required products
Cable Tube CT - Ø 90 mm length 150 mm
Article number
01279101
Cable Tube CT - Ø 120 mm length 150 mm
Article number
01271151
Cable Tube CT - Ø 90 mm length 200 mm
Article number
01279201
Cable Tube CT - Ø 90 mm length 300 mm
Article number
01279301
Cable Tube CT - Ø 120 mm length 200 mm
Article number
01271201
Cable Tube CT - Ø 60 mm length 150 mm
Article number
01276101
Cable Tube CT - Ø 120 mm length 300 mm
Article number
01271301
GFM - Fire protection mortar, 25 kg bag
Article number
01167000
FLAMMOTECT-A - Filler, 12.5 kg
Article number
01155134
FLAMMOTECT-A - Filler, 310 ml
Article number
01155115
FLAMMOTECT-A -
Article number
01155153
Mineral wool - 10 kg bag
Article number
01183000
Identification Label, Europe -
Article number
14003