The fireproof wrap of the System NBR-plus used for the fire sealing of various pipelines in a wall cross-section.
Pipe seals

System NBR-plus

The System NBR-plus is a firestop pipe penetration sealing system made of a separable fireproof wrap for non-combustible pipes and pipelines with FEF insulation and glass wool insulation as well as HVAC split lines. Fire-resistant up to max. 120 minutes.

Areas of application

Sealing of pipe penetrations in:

  • Plasterboard walls (≥ 100 mm)
  • Solid walls (≥ 100 mm)
  • Solid floors (≥ 150 mm)
  • Timber construction (CLT walls and CLT floors)

Highlights

  • Sealing of insulated non-combustible pipes with outer diameters up to 323.9 mm and HVAC split lines
  • Single-product solution
  • Low material requirements in walls (separation of the wrap) and floors (only installed on the underside)
  • Annular gap seal with various materials (e.g. mortar or plaster)
  • Sealing of all customary elastomeric foam insulations (FEF)

Fire resistance class

Max. EI 120 acc. to EN 13501-2

Certificate

: 7/2/24

Features

  • Weather-resistant to moisture, freeze-thaw cycles, and UV radiation (use category X)
  • Intumescent inner coating and resistant outer glass fabric
  • Can be coated over
  • Flexible material for easy application and wrapping of pipelines

Downloads

Application data sheets / Installation manuals / Certificates

Installation video: System NBR-plus

The System NBR-plus fire protection tape offers an effective solution for sealing off insulated non-combustible pipes up to an external diameter of 323.9 mm and air conditioning split ducts. Due to the division of the tape, only a small amount of material is required to install the seal. The NBR-plus system fulfils the requirements of the fire resistance class up to EI 120 in accordance with EN 1350-2.

System NBR-plus

System information

Technical data

Thickness of building element

Building element

Plasterboard wall

Thickness of building element

≥ 100 mm


Building element

Solid wall

Thickness of building element

≥ 150 mm


Building element

Solid floor

Thickness of building element

≥ 150 mm

Data line

General

Types of insulation

XG/Armaflex, SH/Armaflex, AF/Armaflex, NH/Armaflex, Kaiflex KKplus s2, Kaiflex HTplus, Isover ML 3, Isover U Protect, Armacell Armalok, Armaflex Ultima

HVAC split line combinations

yes

Non-combustible pipes Ø

Building element

Plasterboard wall, solid wall, solid floor

Diameter Ø

≤ 323.9 mm

Insulation

FEF

Material/manufacturer

Steel


Building element

Plasterboard wall, solid wall, solid floor

Diameter Ø

≤ 88.9 mm

Insulation

FEF

Material/manufacturer

Copper


Building element

Solid floor

Diameter Ø

≤ 219.1 mm

Insulation

Glass wool

Material/manufacturer

Steel


Building element

Solid floor

Diameter Ø

≤ 88.9 mm

Insulation

Glass wool

Material/manufacturer

Copper


Building element

Solid floor

Diameter Ø

≤ 54 mm

Insulation

PUR

Material/manufacturer

Steel

Pre-insulated bundled pipes type C-I Ø

Building element

Plasterboard wall, solid wall, solid floor

Diameter Ø

≤ 18 mm

Required products

NBR-plus - NBR-plus fire protection fabric, roll, 10 metres, width 125 mm, pre-slotted (2 x 62.5 mm)

Article number

01261941

FLAMMOTECT-A - Filler, 12.5 kg

Article number

01155134

FLAMMOTECT-A - Filler, 310 ml

Article number

01155115

NOVASIT BM - Fire protection compound, 20 kg bag

Article number

01161000

NOVASIT BM - Fire protection compound, 10 kg pail

Article number

01161010

GFM - Fire protection mortar, 25 kg bag

Article number

01167000

Lamella mat KLIMAROCK - Roll 610 x 50 cm = 3.05 m²

Article number

01187100

Mineral wool - 10 kg bag

Article number

01183000

Do you have questions on System NBR-plus and other fire protection applications? Please contact us: