CT Cable Tube
Cable Tube CT consists of two half shells with an inner lining made of intumescent fire protection fabric with full-surface adhesion. A soft foam plug set intended for the system is also available.
Use: Cable Tubes CT are used as a firestop tubing for cable penetration seals.
Areas of application
Cable Tubes CT are used in plasterboard walls as well as solid walls and floors and are used for the fire-resistant sealing of:
- Cables
- Cable bundles
- EIC bundles with/without cables
- PVC-U pipes
- Bundled or single “gabocom speed-pipe” PE pipes (glass fibre cables and microcables)
- HVAC split line combinations
Highlights
- Particularly easy to use for the construction of single penetration seals in core drill holes
- Can also be installed in existing installations
- 100% occupancy of the Cable Tube cross section possible
- New: now also tested for sealing cables, cable bundles, EIC bundles with/without cables, and HVAC split line combinations in timber construction
Used for system
Features
- Available in various diameters and lengths
- Quick and clean installation
- No reveals required in plasterboard walls
- Group arrangements with zero clearance possible
Downloads
Technical data sheets / Safety data sheets / Declaration of performance
Product information
Technical data
General
Product category
Cable tubes / -boxes
Product description
Cable tube consisting of two half-shells with intumescent inlay
Fields of application
- Used as a single penetration seal
- Used as a provision for future installations
- Used in lightweight partition walls, solid walls and solid floors
Brand name
Flamro
Colour
Grey
Material
Half shells made of PVC. Inner lining made of intumescent fabric. Closure with soft foam plugs.
Half-shell closure
Snap fastener
Sound insulation properties
64 (-2;-6) dB Dn, e; Dn, w (C; Ctr)
Storage
Protect from frost! Store in a cool and dry place (+5 °C – +30 °C).
Safety notes
No hazardous material according to German Hazardous Substances Act (GefStoffV) and no hazardous material according to German Act on the Transport of Dangerous Goods (GGVS/ADR).
Safety & Sustainability
Emissions measurements & assessments
Label
Test objective/standard
AgBB scheme
Certificate/test report number
392-2022-00235701_D_EN
Summary / Evaluation
passed
Label
Test objective/standard
French-VOC
Certificate/test report number
392-2022-00235701_E_EN
Summary / Evaluation
A+
Test objective/standard
Byggvarubedömningen (Construction product assessment Sweden)
Certificate/test report number
392-2022-00235701_C_EN
Summary / Evaluation
Recommended
Delivery and packaging
CT Cable Tube - Ø 120 mm length 150 mm
Article number
01271151
Color
Grey
CT Cable Tube - Ø 120 mm length 200 mm
Article number
01271201
Color
Grey
CT Cable Tube - Ø 120 mm length 300 mm
Article number
01271301
Color
Grey
CT Cable Tube - Ø 60 mm length 150 mm
Article number
01276101
Color
Grey
CT Cable Tube - Ø 90 mm length 150 mm
Article number
01279101
Color
Grey
CT Cable Tube - Ø 90 mm length 200 mm
Article number
01279201
Color
Grey
CT Cable Tube - Ø 90 mm length 300 mm
Article number
01279301
Color
Grey