System ECP
The ECP system offers a range of solutions for fire-sealing combustible and non-combustible pipes. It is also ideal for complex installation scenarios such as 2x45° bends, sockets, diagonal pipes and pipes with little clearance from the building structure. Fire resistance rating up to a maximum of 120 minutes.
Areas of application
Ideal for sealing various installation pipes in:
- Plasterboard walls
- Solid walls
- Solid floors
Highlights
- One collar suitable for almost any seal up to a diameter of 160 mm
- The collar is particularly slim with a height of only 9 mm – an ideal solution for confined spaces
- Maximum flexibility also for special solutions, such as 2 × 45° bends with zero clearance to the building element, pipe couplings, diagonally installed pipes, HVAC split line combinations and electrical installation conduits
- Quick and easy installation without sheet metal sheathing
Fire resistance class
Max. EI 120 acc. to EN 13501-2
Certificate
ETA-26/1247: Jun 23, 2026
Features
- Approved for various types of pipes, such as combustible pipes, non-combustible pipes (steel, stainless steel, cast iron), HVAC split lines, and beverage pipes
- Tested for plastic pipes with PE sound insulation tubing
Downloads
Application data sheets / Installation manuals / Certificates
System information
Technical data
General
Brand name
Flamro
Thickness of building element
Building element
Flexible wall
Thickness of building element
≥ 100 mm
Building element
Rigid wall
Thickness of building element
≥ 100 mm
Building element
Rigid floor
Thickness of building element
≥ 150 mm
Data line
Combustible pipe Ø
Building element
Flexible wall
Diameter Ø
≤ 125 mm
Material/manufacturer
REHAU RAUPIANO PLUS
Building element
Flexible wall
Diameter Ø
≤ 125 mm
Material/manufacturer
REHAU RAUPIANO LIGHT
Building element
Flexible wall
Diameter Ø
≤ 125 mm
Material/manufacturer
Conel Drain
Building element
Flexible wall
Diameter Ø
≤ 160 mm
Material/manufacturer
Geberit Silent-db20
Building element
Flexible wall
Diameter Ø
≤ 160 mm
Material/manufacturer
Geberit Silent PP
Building element
Flexible wall
Diameter Ø
≤ 160 mm
Material/manufacturer
Geberit Silent Pro
Building element
Flexible wall
Diameter Ø
≤ 160 mm
Material/manufacturer
Wavin AS+
Building element
Flexible wall
Diameter Ø
≤ 160 mm
Material/manufacturer
KE KELIT PHONEX AS PLUS
Building element
Flexible wall
Diameter Ø
≤ 125 mm
Material/manufacturer
Wavin SiTech+
Building element
Flexible wall
Diameter Ø
≤ 125 mm
Material/manufacturer
POLO-KAL NG
Building element
Flexible wall
Diameter Ø
≤ 125 mm
Material/manufacturer
POLO-KAL XS
Building element
Flexible wall
Diameter Ø
≤ 160 mm
Material/manufacturer
POLO-KAL 3S
Building element
Flexible wall
Diameter Ø
≤ 125 mm
Material/manufacturer
Silenta Premium
Building element
Flexible wall
Diameter Ø
≤ 125 mm
Material/manufacturer
Ostendorf HT Safe
Building element
Flexible wall
Diameter Ø
≤ 160 mm
Material/manufacturer
Ostendorf Skolan Safe
Building element
Flexible wall
Diameter Ø
≤ 160 mm
Material/manufacturer
Pipelife MASTER 3 PLUS
Building element
Flexible wall
Diameter Ø
≤ 110 mm
Material/manufacturer
Uponor decibel
Building element
Flexible wall
Diameter Ø
≤ 125 mm
Material/manufacturer
Valsir Blackfire
Building element
Flexible wall
Diameter Ø
≤ 125 mm
Material/manufacturer
Valsir Triplus
Building element
Flexible wall
Diameter Ø
≤ 160 mm
Material/manufacturer
PE-HD, ABS, SAN+PVC
Building element
Flexible wall
Diameter Ø
≤ 160 mm
Material/manufacturer
PVC-U, PVC-C
Building element
Flexible wall
Diameter Ø
≤ 50 mm
Material/manufacturer
aquatherm green pipe MF-RP
Building element
Flexible wall
Diameter Ø
≤ 50 mm
Material/manufacturer
aquatherm blue pipe MF-RP
Preassembled electrical conduits Ø
Building element
Flexible wall
Bundle Ø
≤ 172 mm
Single Ø
≤ 63 mm
Cable Ø
≤ 28 mm
Single electrical conduit Ø
Building element
Flexible wall
Single Ø
≤ 63 mm
Cable Ø
≤ 28 mm
General
Split HVAC line combinations
Tubolit DuoSplit copper pipes, PVC hose, cable
Multilayer pipe Ø
Building element
Flexible wall
Diameter Ø
≤ 63 mm
Insulation
FEF (flexible elastomeric foam)
Material/manufacturer
Geberit Systemrohr ML
Non-combustible pipes Ø
Building element
Flexible wall
Diameter Ø
≤ 139.7 mm
Insulation
Glass wool (mineral insulation made of glass fibres)
Material/manufacturer
Steel, stainless steel, cast iron
Tube bundles
Building element
Flexible wall
Diameter Ø
≤ 75 mm
Type
Geberit Systemrohr ML
Required products
ECP Endless Collar -
Article number
0337600000